The flow rate of a faucet or shower head is measured in gallons per minute (GPM) and is a critical factor in sizing a Bosch tankless water heater, or for evaluating if an older fixture is wasting water.
The Federal Energy Policy Act of 1992 required all faucet and shower fixtures made the USA to have a flow rate of no more than 2.2 GPM at 60 PSI. Often you can get below 2.2 GPM with low flow aerators. However before 1992, older fixtures used much more water than 2.2 GPM, sometimes upward of 10 GPM. So before any calculations for water heater sizing can properly be done an accurate measurement of a fixture's flow rate should be done. If any fixture is much more than 2.2 GPM, it is a good candidate for replacement with a new code compliant water efficient fixture.
Here's how to quickly determine flow rate for a specific faucet or shower head:
For sizing of a tankless water heater you would want to determine the most applications (uses) at one time you would be using in the worst cases scenario. As an example, You normally run 2 showers at the same time and the laundry going too. Each shower flows 2.0 GPM and the Laundry flows 1.5 GPM so that would be a total of 5.5 gpm. Using this calculation you can then find a unit that would give you at least 5.5 gpm with an output temperature of 116 degrees or better.
You can call us at 888-726-9752 for help with sizing a Bosch tankless water heater.